Single phase, Single phase zero
crossing, Two-wire three-phase zero crossing (SP, SZ, TZ)
Connector Pin |
Connector
No. |
Description |
Notes |
TB-01 |
FS |
Detection of the fuse burn down |
Do not connect |
TB-02 |
M |
+5VDC |
Only for this control board, not
for other use
positive control signal input. |
TB-03 |
+ |
Positive control signal input |
The default setting is 4~20mA
when the
sticker is not marked. |
TB-04 |
- |
Standard and analog signal
voltage |
TB-05 |
E3 |
Connected to the VR 3rd pin of
the outside potentiometer |
Adjustable output 0~100%, Please
eliminate
the shorted copper wire between E3 and E2
when
using the outside potentiometer with
VR. (2~10KΩ) |
TB-06 |
E2 |
Connected to the VR 2rd pin of
the outside potentiometer |
TB-07 |
E1 |
Connected to the VR 1st pin of
the outside potentiometer |
TB-08 |
NC |
Alarm connector output (normal
close) |
Connector capacity |
227VAC 2A. |
TB-09 |
COM |
Alarm connector output (Common
point) |
125VAC 2A. |
TB-10 |
NO |
Alarm connector output (normal
open) |
30VAC 2A. |
TB-11 |
AC1 |
Auxiliary power source |
Please refer to the stick for
the auxiliary
power and voltage. |
TB-12 |
AC2 |
Three-wire three-phase angle,
Three-wire three-phase zero crossing (TP, ZZ)
Connector Pin |
Connector
No. |
Description |
Notes |
TB-01 |
• |
Empty pin |
Do not connect |
TB-02 |
M |
+5VDC |
Only for this control board, not
for other use
positive control signal input. |
TB-03 |
+ |
Positive control signal input |
The default setting is 4~20mA
when the
sticker is not marked. |
TB-04 |
- |
Standard and signal voltage |
TB-05 |
E3 |
Connected to the VR 3rd pin of
the outside potentiometer |
Adjustable output 0~100%, Please
eliminate
the shorted copper wire between E3 and E2
when
using the outside potentiometer with
VR. (2~10KΩ) |
TB-06 |
E2 |
Connected to the VR 2rd pin of
the outside potentiometer |
TB-07 |
E1 |
Connected to the VR 1st pin of
the outside potentiometer |
TB-08 |
NC |
Alarm connector output (normal
close) |
Connector capacity |
227VAC 2A. |
TB-09 |
COM |
Alarm connector output (Common
point) |
125VAC 2A. |
TB-10 |
NO |
Alarm connector output (normal
open) |
30VAC 2A. |
TB-11 |
AC1 |
Auxiliary power source |
Please refer to the stick for
the auxiliary
power and voltage. |
TB-12 |
AC2 |
Applicable high-speed fuse for
the power regulator
Rated current |
30A |
45A |
60A |
80A |
100A |
Fuse |
40FE |
63FE |
80FE |
100FE |
660GH-125 |
Brand |
Bussmann |
Bussmann |
Bussmann |
Bussmann |
HINODE |
Rated current |
125A |
150A |
180A |
230A |
300A |
Fuse |
80FE*2 |
100FE*2 |
660GH-125*2 |
250FM |
315FM |
Brand |
Bussmann |
Bussmann |
HINODE |
Bussmann |
Bussmann |
Rated current |
380A |
450A |
580A |
720A |
Fuse |
660GH-400 |
250FM*2 |
315FM*2 |
660GH-400*2 |
Brand |
Bussmann |
Bussmann |
Bussmann |
HINODE |
|
A ONE UNION CO., LTD.
5F, No. 99, Sec. 3, Nangang Road.,
Nangang District, Taipai City 115 63, Taiwan
TEL : +886-2-27882828 FAX : +886-2-27882727
URL : www.aone.com.tw |
|