About UsCatalogContact UsProduct EquipmentHow to make thermocoupleFEPHome
Our Product
Thermocouple
Thermocouple Head & Terminal Block
Surface Temperature Probe Series
Thermocouple Extension Wire
Special Thermocouple Extension Wire
Thin Film Platinum Resistance Temperature Detector
Product Equipment
MI Cable End Stripping Machine
HAN-128
Splicing Machine TC-06
Straightening Machine
Pneumatic Air Clamps HAN-100
Hydrogen-Oxygen Welding Machine
Pneumatic Crimping Machine AM-10
Cold End Pressing Machine CLX-Y01
Automatic Wire - cutting machine
Wire Stripper for metal braiding
HAN-200
Wire Stripper LL-305
Automatic Coil Winding Machine
HAN-55
Twisting Tie Machine BW-1020
Wire frame SC Series
Name-Plate Printer
How to make thermocouple
Demonstration
Accessories
Protection Tube
SUS 304 Terminals
Stainless Steel Tube
Connector
Spiral coiled wire
Accessories for Industrial Instrument
Related Products of
Electric-Heat
SCR Power Regulator Phase Controller Series
Cartridge Heater
Infrared Ceramic Heaters
Female Plugs for Heatrs
750℃ High Temperature Electric Wire
Instrument
Reach Micro Processor Temperature Controller
Infrared Thermometer
1326-1327-1327K
Digital Thermometer
Temperature Transmitter
Microprocessor Calibrator / Thermometer
Galileo Color-Ball Thermometer

THYRISTOR POWER REGULATOR

Mounting Dimensions

Product Features:

The SCR unit attached with high speed fuse in order to prevent the damage of SCR due to the    shortage current (di/dt).
The unit is packagecd onstruction with less dimension, easy for installation and wiring
The causes of malfuntion can be indicated by individual LED lamp, easy for trouble shooting.
Less non-linearity output provides accurate control of temperature.
High quality and high technical productions with no electrical interference.

Operation Enviroment:
Ambient temperature:-10~45,Relative humidity: Max 90%
Installation: 
The SCR unit will produce heat itself during operation, piease errect it
   upward accrding to the instruction.
The panel must be upward ventilated for hot air. we recommand 
   mountiong a ventilating fan in the control panel.
Do nor install the unit in the space with high temperature and poor 
   ventilating, Do not operate the unit exceed 70% of rated output in
   case of above mentioned poor ambient  conditions.
Load Test:
The SCR unit will not well funtioned in case of less output load(0.6 Amp).
   Please connect the load at least 0.6 Amp.

Comparation of control mode and output wave:

LED lamp indication and trouble shooting:

Pos.No Color Indicating condition Causes of malfunction Treament and trouble shooting
PL
(L1)
Green 
No indication of power
supply lamp
Lamp lighting means
normal
@No power of Aux. source.
@Malfuntion on PCB board.
@Over temperature of SCR.

@Check the Aux.power supply.
@Repair or replace the PCB board.
@Check the SER temperature.

IN
(L2)
Green
No indication of input lamp

Lamp lighting means normal

@No output signal from TIC
@Output signal from TIC is 
    reverse.
@Max value of internal output
    or External VR is zero setted.

@Check the output signal of TIC.
@Reverse the connect wiring of 
    TIC.
@Check the setting of internal
    and external VR output.

OUT
(L3)
Red
No indication of output lamp.
Phase angle control--
lamp lighting means normal
Aero crossing control--
lamp blinks means normal

@No output signal from TIC or 
    reverse the connecting of 
    output signal.
@Lamp IN lighting and lamp 
   OUT no indication.
@Lamp OUT lighting but no
    current output.

@Check the lamp IN,No indication
    means no output signal from 
    TIC or reverse wired.
@Repair or replace the PCB board
    in case of the nalfunction from
    the board.
@Check main power supply or 
    fuse.

ERR
(L4)
Yellow
Over-temp of SCR lamp light
Lamp lighting means SCR
over temp

@Malfunction or dirt blocking 
    on the ventilation fan. 
@High ambient temperature or 
    poor ventilation.

@Replace or clean the dirt of the
    impeller.
@Improve the ventilation
    condition.